logoGlobal Energy Interconnection

Contents

Figure(0

    Tables(0

      Global Energy Interconnection

      Volume 3, Issue 3, Jun 2020, Pages 205-216
      Ref.

      Coordinate control strategy for stability operation of offshore wind farm integrated with Diode-rectifier HVDC

      Lijun Xie1 ,Liangzhong Yao2 ,Fan Cheng1,2 ,Yan Li1 ,Shuai Liang2
      ( 1.China Electric Power Research Institute,Haidian Dsitrict,Beijing 100192,P.R.China , 2.School of Electrical and Electronic Engineering and Automation,Wuhan University,Wuchang District,Wuhan 430072,P.R.China )

      Abstract

      Due to low investment cost and high reliability,a new scheme called DR-HVDC (Diode Rectifier based HVDC) transmission was recently proposed for grid integration of large offshore wind farms.However,in this scheme,the application of conventional control strategies for stability operation face several challenges due to the uncontrollability of the DR.In this paper,a coordinated control strategy of offshore wind farms using the DR-HVDC transmission technology to connect with the onshore grid,is investigated.A novel coordinated control strategy for DR-HVDC is proposed based on the analysis of the DC current control ability of the full-bridge-based modular multilevel converter (FB-MMC) at the onshore station and the input and output characteristics of the diode rectifier at the offshore.Considering the characteristics of operation stability and decoupling between reactive power and active power,a simplified design based on double-loop droop control for offshore AC voltage is proposed after power flow and voltage–current (I–V) characteristics of the offshore wind farm being analyzed.Furthermore,the impact of onshore AC fault to offshore wind farm is analyzed,and a fast fault detection and protection strategy without relying on communication is proposed.Case studies carried out by PSCAD/EMTDC verify the effectiveness of the proposed control strategy for the start up,power fluctuation,and onshore and offshore fault conditions.

      1 Introduction

      The voltage source converter based on high-voltage direct current (VSC-HVDC) transmission technology has attracted increasing attention because of its advantages such as flexible control,supply to passive system,and the need for few filter banks; further,it has gained popularity for use in offshore wind farm integration [1–2].The AC voltage control of offshore wind farm is important to ensure the transmission of offshore wind power,and it is controlled by the rectifier converter at the transmission end in the VSCHVDC schemes [3–6].An alternative control strategy for offshore voltage control is proposed,wherein a voltage control strategy developed in a microgrid [7–12]is applied to wind turbines,which enables the wind turbines to operate as grid forming units and provide voltage and frequency control [13–15].However,when the wind turbines operate in a grid forming unit,it is difficult to achieve the maximum power tracking without auxiliary components.

      Recently,a new topology called DR-HVDC transmission was proposed to deal with offshore wind farm integration with advantage of low cost and high reliability [16–17].The wind farm can operate at maximum power point tracking without auxiliary components when the DR topology is combined with the voltage control strategy of wind turbines.Different strategies have been proposed for wind turbine control,including centralized control [17–19],synchronous control based on GPS signals [20–21],master–slave control [22–24],and droop control [25–27],which are similar to strategies developed in the micro grid.

      The droop control used in [25–27],which uses the local signal and achieves hot-plug,is more easy to implement [7–9].However,the droop control methods utilize P–V and Q–f droop characteristics to control active and reactive power flows,and they are characterized by slow dynamics and the coupling of active and reactive power.Droop control is divided into single-loop droop control and multi-loop droop control [7–9].The latter is prone to being less damped and experiencing instability more easily especially in a highpower converter,with negative damping synthesized by the inner current loop at certain harmonic frequencies [25–26].Therefore,multi-loop control schemes can hardly meet the requirement of voltage waveform quality.

      In the DR-HVDC transmission scheme,the onshore converter operates as a voltage source,and the wind farm and rectifier operate as a current source [17–27].However,this coordinated control is problematic once a DC fault occurs,and an additional control strategy or equipment is required.

      The linear relationship of diode rectifier between the input and output and DC current control ability of the onshore converter is analyzed,and it provides new insight into the control of the DR-HVDC system.A coordinate control strategy is proposed for DR-HVDC system.With DC current being controlled by onshore converter and power flow analysis of offshore wind farm,a simplified control strategy for wind turbines based on I–V droop characteristics is designed and analyzed with the stability improvement of the AC voltage of offshore wind farms,which also decouples the active and reactive power.A new insight of frequency control is proposed based on Park transmission.A current-error-dependent fault protection is used to protect converters from the overcurrent via regulation of the voltage of the wind turbine during fault transients because the inner current loop is eliminated.The proposed control strategy allows for the synchronization of wind turbines,reactive power sharing without communications between wind turbines,fast response once fault occurs,and fast recovery after the fault is cleared.

      The remainder of this manuscript is organized as follows: The mathematic model in the dq axis of the offshore wind power system is presented in Section 2.A simplified voltage controller based on I–V droop characteristics is proposed with protection schemes in Section 3.Section 4 presents the simulation model built in PSCAD/EMTDC to verify the controller.Finally,the conclusions of this study are provided in Section 5.

      2 Model of the offshore wind farm and DR-HVDC

      Fig.1 Topology of wind farm integrated by diode-based rectifier

      The offshore wind farm collected by DR is shown in Fig.1,and it consists of several wind turbine (WT) clusters.Each cluster comprises fully rated converter-based WTs.The offshore AC grid is connected to the offshore DC grid with a 12-pulse diode rectifier that comprises two 6-pulse diode bridges,thereby enabling better power quality at the collection point of the AC grid.Further,reactive power compensation and harmonic filtering is achieved by the capacitor and filter banks.The pulse of the diode rectifier can be increased to cut the weight and size of platform further because the volume of the harmonic filters is less; however,it will increase the difficulty of transformer design and investment.Only a 12-pulse diode rectifier is used in this paper.

      The MMC technique is selected for future VSC-based HVDC grids.The FB-MMC not only can block DC faults but also provide flexible control because of the negative voltage generating capability [5–6]; it is used in this study.

      Following the criterion of connecting the wind farms into power grid,the wind power system should provide active power and reactive power control.A permanent magnet synchronous generator (PMSG) is used as the wind turbine generator,cascaded with a fully rated AC/DC rectifier as machine side converter (MSC) and a DC/AC inverter as grid side converter (GSC) based on IGBT.Unlike a conventional wind power system,the GSC needs to achieve the control of AC voltage at the collection point,as the rectifier station cannot control the AC voltage of offshore wind farms.To maintain the power balance of wind power system,the MSC of wind turbine is used to control the DC link voltage.

      2.1 Onshore converter based on FBMMC

      Fig.2 Diagram of FBMMC

      The diagram of FBMMC is shown in Fig.2; FBMMC it is composed of six arms,and each arm includes 2N sub-models and arm inductors Ls.vap and van are the output voltages of the upper and lower arms of phase A,respectively,and iap and ian are the currents of the upper and lower arms of phase A,respectively.

      As the output voltage of the sub-model of FB-MMC can be −vc,0,and +vc,DC voltage of FB-MMC can be controlled from Vdc to-Vdc[28–31],making the FB-MMC can be in current source converter mode or an voltage source converter.Consider the output voltage of phase A as an example.

      where ua is the AC voltage of the FB-MMC,Vdc is DC voltage of the FB-MMC,and uacm is the common-mode voltage used to control the circulation current.

      From the DC side,according to KVL

      The dc-link dynamic can be directly controlled by controlling sub-model capacitor voltage.

      2.2 Offshore rectifier based on diode

      The relationship of the average DC voltage of the diodebased bridge VRdc and the AC voltage VF and DC current Idc is

      where LTR is the reactance of the diode rectifier transformer,ωF is the frequency of the offshore system,Vdc is the DC voltage of the onshore converter,R is the equivalent resistance of the HVDC link,B is the number of the 6-pulse diode rectifier,and N is the ratio of the transformer.According to (3),VF is linear with VRdc and Idc,and the diode rectifier conducts only when VF is higher than the threshold value because VRdc must be larger than zero.

      Ignoring the loss of the rectifier,the active power and reactive power is

      From (3) and (4),the relationship between the active power and VF is shown in Fig.3.The VF increases with an increase in active power,and the amplitude of the AC voltage is only changed from 1 to 1.03 pu when the active power output of the wind farm changes from 0 to the rated value with Idc being fixed.In addition,if Idc is changed,the active power will also change.

      Fig.3 Relationship among active power and AC voltage and DC current

      The LTR causes a commutation voltage drop in the output DC voltage.This drop can be represented as resistance ru located at the DC side.As the commutation effect is moved to the DC side neglecting the harmonics of system,the following dq mathematical model is derived [27,28,32].

      where Idrac is the input current of the diode rectifier,δis the angle between VF and the d axis,and φ is the angle between VF and Idrac.Note that Idrac can be determined by Idc,which provides a new possibility for DR-HVDC.

      2.3 Grid side converter of PMSG

      The detailed GSC is shown in Fig.4,where the LC filter and transformer are included.The LC filter is used to ensure a low harmonic current injection to the grid.

      Fig.4 Details of grid side converter

      The dynamic equation of the capacitor voltage vector,inductance,and collection line expressed in the dqsynchronous reference frame is

      where Cf is the filter capacitor,Vo is the output voltage,Io is the output current of GSC,and Il is the current of filter inductance.Further,Rf and Lf are the respective equivalent resistance and inductance,Vcdq is the modulation voltage of converter,RL and LL are the respective equivalent resistance and inductance,and IF is the current of collection line.

      When the reactive compensation capacitor is considered,the angle between Idracd and VF is zero; that is,Idracq=0.According to (4) and (5),the equivalent circuit in the synchronously rotating dq frame is as shown in Fig.5,which is easier to analyze and simplify.Further,the diode rectifier station can be considered as a voltage-dependent current source.

      Fig.5 Simplification of equivalent circuit considering Idracq=0

      3 Control strategy for stability operation of offshore wind farm integrated with DR-HVDC

      3.1 Control strategy of onshore converter

      1) DC link current control

      According to (3),the onshore converter can be operated as a voltage source or a current source.

      The control of the dc-link current is illustrated in Fig.6.A close loop is used to regulate the dc-link current Idcto its reference Idcref,and to generate the DC voltage reference Vdcref.The DC fault can be cleared by setting Idcref to zero without blocking MMC if a DC fault occurs.The submodel voltage vc is controlled to its reference value (vc_ref) by adjusting the active power current Id.The reactive power Q is regulated to its reference Qref.Current vector control is used to regulate the AC current Idq of MMC to its reference Idqref and to generate the AC voltage reference Uabcref.A circulating current is used to optimize the converter properties and generate common-mode voltage reference uacmref; it is not illustrated here.

      2) Start up

      According to (4),VRdc will increase with the power transmitted by DR-HVDC with a fixed Idc and VF. To accelerate the AC voltage and decrease the power losses caused by the smaller the DC link current,a start up strategy for FBMMC is used.

      where VdcN is the nominal DC voltage of the onshore converter.

      3) Onshore fault protection

      Once an onshore fault occurs,the MMC will not be able to deliver active power to the load.In general,the DC capacitor will be charged,and the DC voltage will rise rapidly because the offshore wind farm will keep delivering power.

      However,the dc-link current is controlled in this study.Once the AC fault occurs,the current loop in Fig.6 will saturate,and it would make the sub-model voltage controller invalid.The DC capacitor will then be charged,and the sub-model voltage will increase,while the DC voltage remains almost unchanged because the linear relationship between DR and the AC voltage is controlled by WT.It is difficult for offshore wind farm to detect the onshore fault without communication as no obvious local variables can be detected.And semiconductor devices will be destroyed without an additional protection strategy.Here,a protection strategy for the onshore fault is proposed.

      Fig.6 Control block for onshore MMC converter

      3.2 Control strategy of GSC

      As mentioned before,the offshore wind turbines take the responsibility of voltage and frequency control,and power control.A simpler and faster controller of the gridside converter of PMSG is proposed for GSC considering the onshore converter:

      1) Power controller

      Because the WT cluster is usually connected with parallel wind power systems,there should be a coordinated control strategy between the WTs to supply the required power without any communications among converters; therefore,droop controls are implemented [11,30].

      The instantaneous active and reactive power are calculated as

      To gain a higher quality of power being injected into grid,a one-order low-pass filter with a cut-off frequency ωc is used [30–31].The average active P and reactive power Q are obtained as

      According to (10),the power droop control are intrinsically low band-width controllers with slow dynamics [33–34].When voltage orientation is considered,the active power is proportional with iod,and the reactive power is proportional with the ioq.

      At the steady state,the relationship of the output voltage of the GSC,the ac voltage at the collection point and the current can be derived from (6).

      Equation (11) implies that the I–V characteristics of the converter that IFdi and IFqi are related to the output voltage of the converter because VF is clamped by the diode rectifier according to (3).Therefore,power sharing between converters can be achieved by adjusting the output voltage of converters.

      The power flow of the collection line can be rewritten as

      As Ioq is very small,it can be found that the output voltage of GSC is determined by Iod,and the frequency is related to the voltage difference of the q component.To achieve faster dynamics,the I–V based droop controller is adapted here according to (11) and (12).

      where is the reference value of the d-axis current and it is calculated by is the reference of reactive power and it is designed to be zero,where Vo-ref is reference value of AC offshore voltage; VoN is the rated value; ωFN is rated frequency value; and Kq is the droop coefficient that is selected based on the power rating of wind turbines to avoid current circulation.

      This I–V droop controller simplifies the nonlinear control problem of the active and reactive sharing,and it will not influence by the parameters of the line,which decouples reactive and active powers further.In addition,with the inherent filter of the active and reactive power measurement being eliminated,the system reacts quickly to power changes.

      2) Voltage controller

      According to (6),the open-loop output-voltage dynamics can be derived as

      As the I–V controller is used,a single-loop voltage controller is adopted without the current controller for simplification.Equation (14) shows that the output voltage belongs to a second-order system.To achieve good tracking of the output voltage,we propose the following controller expression.

      For a 100 MW wind farm with parameters as listed in Table1,the PID parameters of the voltage loop are Kvp = 1,Kvi = 100,and KvD = 0.0001.Considering only the d-axis,the control block diagram and bode plot of the transfer function is shown in Fig.7 and 8.The system shows a gain margin of infinity and a phase margin of 32° with a bandwidth of 1030 Hz.

      Fig.7 Control block of AC voltage

      Fig.8 Bode analysis for the voltage controller

      3) Frequency controller

      The three phase utility voltages can be rewritten in the synchronous reference frame using the PLL output θ* as

      The difference of the angle is very small; therefore,the equation can be rewritten as

      The angle is the integration of frequency,that is,

      A PI controller is designed for frequency control.A new control strategy is proposed; this strategy combines droop control and Park transformation,and it is easy to design and is closer to the natural characteristics of the droop,as shown by (18).

      For the 100-MW wind farm with parameters as listed in Table1,the PI parameters of frequency loop and PLL are Kwp = 42 and Kwi = 2,and KpPLL = 0.05 and KiPLL = 1.5,respectively.Considering only the q-axis,the control block diagram and bode plot of the open loop is shown in Fig.9 and 10.It can be found that the system has a gain margin of infinity and a phase margin of 170° with a bandwidth of 100 Hz.Therefore,it can be concluded that the system remains stable in the q-axis.

      Fig.9 Block diagram of the frequency control system

      Fig.10 Bode analysis for the frequency controller

      4) Fault protection

      Unlike synchronous generators,the converter does not have any overload capability,and therefore,a large transient current caused by disturbances can damage the valves during the offshore fault.Therefore,a fault protection strategy must be implemented in the control system.Once an overcurrent is detected,the current can be limited by quickly decreasing the voltage reference as shown in (19).The current will be limited as the voltage drop between the output point of the converter and the fault point is decreased.

      In addition,considering frequency control during the fault and to gain a faster recovery after the fault,the frequency axis,i.e.,the q-axis,is kept prior,that is,

      In addition,if the onshore fault occurs,with the strategy of (8),the DC voltage of DR-HVDC will increase,which increases Vo,and here,a fast power reduction is used by the decreasing voltage reference as shown in (19).

      Fig.11 Block of the controller of GSC

      The diagram of the control strategy proposed in this paper is shown in Fig.11,which includes the I–V droop controller generating the voltage reference for the voltage controller and the frequency reference for the frequency controller; further,a single loop controller is used to make the output voltage track the voltage reference.As the inner loop current is eliminated,a current error-based limiter is used to protect from converter overcurrent.

      4 Results

      Simulation models of the HVDC system with the wind farm collected and interconnected by the diode-based rectifier are developed on the PSCAD/EMTDC platform.The topology is shown in Fig.1,and the parameters are listed in Table1.The string is equal to one wind power system,and there are six strings.The total rated power is 1000 MW; there are four strings rated at 200 MW and two strings rated at 100 MW.The distance between each string is 5 km.As a detailed switch mode is time consuming,an average model of the MMC is used in the simulation.

      Table1 Parameters of the simulation system

      Components Parameters Values Wind system Power 200 MW/100 MW Transformer 3.3/66 kV Filter capacitor 0.1 pu Converter reactance 0.15 pu Switching frequency 1.95 kHz Diode based Rectifier Transformer 66/261.8/261.8 kV Leakage inductance 0.2 pu Onshore VSC DC voltage 640 kV DC current 1.5 kA Power 1000 MW Transformer 400 kV/330 kV

      4.1 Start up and steady operation

      Assume that WTs are equipped with an internal power supply such as an uninterruptible power supply (UPS) that can help the WT to supply critical components for very short durations.

      The dc current of the HVDC link is built by onshore MMC first,following which the breaker of the diode rectifier and the filter are closed.The DC current of the grid-side FB-MMC is shown in Fig.12.After the onshore FB-MMC starts up,its DC current is controlled to be 0.After 0.25 s,the DC current of the FB-MMC increases and reaches 0.32 kA.Then,the wind turbine can be started individually,and the offshore AC voltage will be built by the GSC.

      Fig.12 Waveforms of onshore FB-MMC during startup

      The self-startup of wind turbines will work once the wind speed exceeds 4 m/s.When the generator reaches a certain speed,the pitch angle is manually adjusted to 0° from 90° at a speed of 2°/s,which is neglected in the simulation.Once the generator speed reaches the nominal speed,it will be integrated into the grid.Fig.13 and 14 shows the start-up of the system.

      From Fig.13,it can be seen that the first wind farm is started at t = 2.5 s,and the AC voltage is built to 3.3 kV as shown in Fig.13(c) and wind power rated 200 MW is transmitted to the DC grid as shown in Fig.13(a).Then,other wind farms are synchronized and integrated into the DR rectifier one by one at t = 4.5 s,6.5 s,8.5 s,10.5 s,and 13.5 s.With more WTs connected,the reactive power produced by wind farm #1 is reduced and shared with other wind farms according to the droop coefficient,as shown in Fig.13(b).Fig.14 shows the curves at collection point for the corresponding values in Fig.13.At t = 13.5 s,the total power of the wind farm reaches 1000 MW as shown in Fig.14 (a).The active power of the DR increases and the reactive power decreases.

      Fig.13 Performance of the offshore system during start-up of each wind farm

      Fig.14 Performance of the offshore system during start up and steady operation at collection point

      At t = 18 s,the active power reference of wind farm #1 decrease from 200 MW to 100 MW,and the results shows that the output active power follows the reference.The voltage and frequency are shown in Fig.14 (b) and (c),which maintain stable operation.The DC current of the HVDC link follows its reference as stated in (7) and as shown in Fig.14 (e).

      Note that the wind farm started first takes the responsibility of charging the transformer and the reactive compensators,and therefore,a considerable amount of reactive power will be produced by this wind farm.This reactive power is decreased once other wind farms are integrated,and it is finally shared between wind farms according to the droop coefficient.

      4.2 AC Fault of offshore wind farm

      A three-phase grounding fault of the offshore systems occurs at t = 25 s,and it lasts for 0.5 s.The AC voltage of on shore grid quickly reduces to 0,and the current of the wind farm is reduced to a small value owing to voltage protection as shown in Fig.15.Fig.16 and 17 show that the voltage and frequency of system and each wind farm can recover to normal quickly after the fault.

      4.3 DC Fault of offshore wind farm

      A permanent pole-to-pole DC fault occurs at t = 8 s.The DC voltage drops to zero after the DC fault,as shown in Fig.18 (c).The DC current control drops to 0 with the control strategy shown in Fig.7 (b).After the DC shortcircuit fault occurs,because of the coupling characteristics of the DC voltage and the AC voltage,and considering the existence of the leakage reactance of the converter transformer,the AC voltage drops to 0.1 pu,as shown in Fig.18 (b) and (e).That is,during the DC fault,the offshore wind farm adopts low voltage ride-through control; wind farms reduce the output power and disconnect.During the fault,the wind turbine output AC current,which is affected by the current limit control (19),is 1.2 pu,as shown in Fig.18 (f).

      Fig.15 Performance of the offshore system during grounding fault at collection point

      Fig.16 Performance of the offshore system during grounding fault at collection point

      Fig.17 Performance of each wind turbine during grounding fault at collection point

      Fig.18 Performance of the offshore system during DC fault

      Fig.19 Performance of MMC during onshore grounding fault

      4.4 AC Fault of onshore system

      A three-phase grounding fault of the onshore systems occurs at t = 4 s and lasts 0.5 s.The AC voltage of onshore grid quickly reduces to 0 and the current of the MMC increases to its limit at about 1.2 pu as shown in Fig.19.As shown in Fig.19 (b),the current loop remains saturated until the sub-model voltage controller returns to valid.

      As onshore fault stops the transmission of the active power,and there is a difference between the active power of wind farm and the onshore system.The curves of S1 in Fig.20 represent the case without any protection strategy.The curves of S2 in Fig.20 represent the strategy shown in (8),and the curves of S3 represent the strategy shown in (8) and (19).The DC capacitor is charged,and the sub-model voltage increases,as shown in Fig.20(a); the DC voltage remains constant as shown in Fig.20 (b),which makes it difficult to detect onshore fault without communication.When the DC current reduction of S2 is adapted,the DC voltage increases as well as VF,which makes the wind farm experience a high-voltage ride through and the active power decrease automatically.However,the overvoltage of the HVDC link is 1.4 pu.To decrease the overvoltage of the HVDC link,a fast power reduction strategy is used by the wind farm.Curves S3 show a smaller capacitor voltage,smaller DC overvoltage,and a quick response.

      Fig.20 Performance of the DR-HVDC during grounding fault at onshore AC grid

      5 Conclusions

      In this paper,a simplified strategy with a fast response is proposed for PMSG based offshore wind farms integrated with DR-HVDC.

      A new coordinated control strategy for system stability operation of DR-HVDC system is proposed by analyzing the DC current control ability of the FB-MMC and characteristics of the diode rectifier,which has the advantage of flexible capability on DC fault clearing.

      The relationship among voltage,frequency and current of GSC is analyzed and a simplified controller is designed based on the I-V characteristics,which has faster dynamics and more stable.A frequency controller based on Park transformation is designed.As the DC current control of FB-MMC introduces new problem to the onshore AC fault,a protection strategy is proposed,which achieves fast onshore fault detection and power reduction to protect MMC from being destroyed without communication.

      The detailed simulation model in PSCAD/EMTDC is built and various scenarios including the start-up,steady operations and response to fault are simulated.It can be concluded that the proposed control strategy can achieve the goal of synchronization of wind turbines,reactive power sharing without communications between converters,fast response once onshore or offshore fault occurs without overcurrent and overvoltage,and a quick recovery after the fault is cleared.

      Acknowledgements

      The work was supported by State Grid Science and Technology Project “Study on Key Technologies of Large Scale Offshore Wind Power Integrating with Onshore Grid” (4000-202055045A-0-0-00).

      References

      1. [1]

        Andersen BR,Xu L (2004) Hybrid HVDC system for power transmission to island networks.IEEE Trans Power Delivery 19(4):1884-1890 [百度学术]

      2. [2]

        Du C,Agneholm E,Olsson G (2008) Comparison of different frequency controllers for a VSC-HVDC supplied system.IEEE Trans Power Delivery 23(4):2224-2232 [百度学术]

      3. [3]

        Du C,Bollen MH,Agneholm E,Sannino A (2007) A new control strategy of a VSC-HVDC system for high-quality supply of industrial plants.IEEE Trans Power Delivery 22(4):2386-2394 [百度学术]

      4. [4]

        Torres-Olguin RE,Molinas M,Undeland T (2012) Offshore wind farm grid integration by VSC technology with LCC-based HVDC transmission.IEEE Trans Sustainable Energy 3(4):899-907 [百度学术]

      5. [5]

        Liu B,Xu J,Torres-Olguin RE,Undeland T (2010) Faults mitigation control design for grid integration of offshore wind farms and oil & gas installations using VSC HVDC.Paper presented at power electronics electrical drives automation & motion,IEEE,2010 [百度学术]

      6. [6]

        Karaagac U,Mahseredjian J,Cai L,Saad H (2016) Offshore wind farm modeling accuracy and efficiency in MMC-based multi-terminal HVDC connection.IEEE Trans Power Delivery 32(2):617-627 [百度学术]

      7. [7]

        Kallamadi M,Sarkar V (2017) Enhanced real-time power balancing of an AC microgrid through transiently coupled droop control.IET Gener Transm Distrib 11(8):1933-1942 [百度学术]

      8. [8]

        De Brabandere K,Bolsens B,Van den Keybus J,Woyte A,Driesen J,Belmans R (2007) A voltage and frequency droop control method for parallel inverters.IEEE Trans Power Electron 22(4):1107-1115 [百度学术]

      9. [9]

        Alizadeh E,Birjandi AM,Hamzeh M (2017) Decentralised power sharing control strategy in LV microgrids under unbalanced load conditions.IET Gener Transm Distrib 11(7):1613-1623 [百度学术]

      10. [10]

        Rocabert J,Luna A,Blaabjerg F,Rodriguez P (2012) Control of power converters in AC microgrids.IEEE Trans power Electron 27(11):4734-4749 [百度学术]

      11. [11]

        Sahoo SK,Sinha AK,Kishore NK (2017) Control techniques in AC,DC,and hybrid AC-DC microgrid: A review.IEEE J Emerging and Selected Topics in Power Electron 6(2):738-759 [百度学术]

      12. [12]

        Kaviri SM,Pahlevani M,Jain P,Bakhshai A (2017) A review of AC microgrid control methods.Paper presented at 2017 IEEE 8th international symposium on power electronics for distributed generation systems (PEDG),IEEE,Florianopolis,2017,pp.1-8 [百度学术]

      13. [13]

        Belenguer E,Vidal R,Beltran H,Blasco-Gimenez R (2013) Control strategy for islanded operation of offshore wind power plants connected through a VSCHVDC link.Paper presented at IECON 2013-39th annual conference of the IEEE industrial electronics society,2013 [百度学术]

      14. [14]

        Oriol GB,Aragüé-Peñalba M (2016) Operation and control of offshore wind power plants,Wiley-IEEE Press [百度学术]

      15. [15]

        Belenguer E,Vidal R,Blasco-Giménez R,Beltran H,Alfonso JC,Ariño C (2013) Islanded operation and control of offshore wind farms connected through a VSC-HVDC link.Paper presented at international conference on renewable energies and power quality,1,2013 [百度学术]

      16. [16]

        Menke P et al.(2015) 2nd generation DC grid access for large scale offshore wind farms.Paper presented at proceedings of the 14th wind integration workshop,Brussels,Belgium,2015 [百度学术]

      17. [17]

        Blasco-Gimenez R,Ano-Villalba S,Rodríguez-D'Derlée J,Morant F,Bernal-Perez S (2010) Distributed voltage and frequency control of offshore wind farms connected with a diodebased HVDC link.IEEE Trans Power Electron 25(12):3095-3105 [百度学术]

      18. [18]

        Bernal-Perez S,Ano-Villalba S,Blasco-Gimenez R,Rodriguez-D'Derlee J (2012) Efficiency and fault ride-through performance of a diode-rectifier-and VSC-inverter-based HVDC link for offshore wind farms.IEEE Trans Ind Electron 60(6):2401-2409 [百度学术]

      19. [19]

        Seman S,Zurowski R,Taratoris C (2015) Interconnection of advanced Type 4 WTGs with diode rectifier based HVDC solution and weak AC grids.Paper presented at proceedings of the 14th wind integration workshop,Brussels,Belgium,2015 [百度学术]

      20. [20]

        Prignitz C,Eckel HG,Knaak HJ (2016) Voltage and current behavior in a FixReF controlled offshore wind farm using a HVDC transmission system based on uncontrolled diode rectifier units.Paper presented at 2016 18th European conference on power electronics and applications,Karlsruhe,2016 [百度学术]

      21. [21]

        Prignitz C,Eckel HG,Achenbach S,Augsburger F,Schön A (2016) FixReF: A control strategy for offshore wind farms with different wind turbine types and diode rectifier HVDC transmission.Paper presented at 2016 IEEE 7th international symposium on power electronics for distributed generation systems (PEDG),2016 [百度学术]

      22. [22]

        Herrera D,Galván E,Carrasco JM (2017) Method for controlling voltage and frequency of the local offshore grid responsible for connecting large offshore commercial wind turbines with the rectifier diode-based HVDC-link applied to an external controller.IET Electr Power Appl 11(9):1509-1516 [百度学术]

      23. [23]

        Yu L,Li R,Xu L (2018) Distributed PLL-based control of offshore wind turbines connected with diode-rectifier-based HVDC systems.IEEE Trans Power Delivery 33(3):1328-1336 [百度学术]

      24. [24]

        Li R,Yu L,Xu L (2018) Offshore AC fault protection of diode rectifier unit-based HVDC system for wind energy transmission.IEEE Trans Ind Electron 66(7):5289-5299 [百度学术]

      25. [25]

        Wang X,Loh PC,Blaabjerg F (2017) Stability analysis and controller synthesis for single-loop voltage-controlled VSIs.IEEE Trans Power Electron 32(9):7394-4704 [百度学术]

      26. [26]

        Li X,Lin P,Tang Y,Wang K (2018) Stability design of singleloop voltage control with enhanced dynamic for voltage-source converters with a low LC-resonant-frequency.IEEE Trans Power Electron 33(11):9937-9951 [百度学术]

      27. [27]

        Areerak KN,Bozhko SV,Asher GM,De Lillo L,Thomas DW (2012) Stability study for a hybrid AC-DC more-electric aircraft power system.IEEE Trans Aerosp Electron Syst 48(1):329-347 [百度学术]

      28. [28]

        Areerak KN,Bozhko SV,Asher GM,Thomas DW (2008) DQtransformation approach for modelling and stability analysis of AC-DC power system with controlled PWM rectifier and constant power loads.Paper presented at 2008 13th international power electronics and motion control conference,Poznan,2008,2049-2054 [百度学术]

      29. [29]

        Deng Y,Tao Y,Chen G,Li G,He X (2016) Enhanced power flow control for grid-connected droop-controlled inverters with improved stability.IEEE Trans Ind Electron 2016 64(7):5919-5929 [百度学术]

      30. [30]

        An R,Liu J,Wu T,Wang S,Liu B (2017) Analysis and design of cutoff frequency for power calculation low-pass filters in droop control.Paper presented at 2017 IEEE 3rd international future energy electronics conference and ECCE Asia,Kaohsiung,2017,1596-1600 [百度学术]

      31. [31]

        Wang S,Liu Z,Liu J,Boroyevich D,Burgos R (2019) Smallsignal modeling and stability prediction of parallel droopcontrolled inverters based on terminal characteristics of individual inverters.IEEE Trans Power Electron 35(1):1045-1063 [百度学术]

      32. [32]

        Griffo A,Wang J (2012) Large signal stability analysis of ‘more electric’ aircraft power systems with constant power loads.IEEE Trans Aerosp Electron Syst 48(1):477-489 [百度学术]

      33. [33]

        Li Y,Fan L (2017) Stability analysis of two parallel converters with voltage-current droop control.IEEE Trans Power Delivery 32(6):2389-2397 [百度学术]

      34. [34]

        Pasha AM,Zeineldin HH,Al-Sumaiti AS,El Moursi MS,El Sadaany EF (2017) Conservation voltage reduction for autonomous microgrids based on V-I droop characteristics.IEEE Trans Sustainable Energy 8(3):1076-1085 [百度学术]

      Fund Information

      supported by State Grid Science and Technology Project “Study on Key Technologies of Large Scale Offshore Wind Power Integrating with Onshore Grid” (4000-202055045A-0-0-00);

      supported by State Grid Science and Technology Project “Study on Key Technologies of Large Scale Offshore Wind Power Integrating with Onshore Grid” (4000-202055045A-0-0-00);

      Author

      • Lijun Xie

        Lijun Xie received the BEng.degree from HEBEI University of Technology in 2012,and the M.S.degree in power electronic from China Electric Power Research Institute (CEPRI),in 2015.She is currently working toward the Ph.D.degree at CEPRI.Her research interest is large-scale renewable energy integration by DC grid.

      • Liangzhong Yao

        Liangzhong Yao received the M.S and Ph.D degrees in electrical engineering from Tsinghua University,Beijing,China,in 1989 and 1993 respectively.Then,he joined the Institute of Nuclear and New Energy Technology of Tsinghua University,as an Associate Professor from 1993 to 1995,and completed Postdoctoral research in the University of Manchester from 1995 to 1999.After that,he worked as a Senior Power System Analyst in ABB from 1999 to 2004,and a Senior Expert and Technical Adviser in Alstom Grid until 2011.From 2012 to 2017,he served as Associate Dean of China Electric Power Research Institute.He is currently a Professor of Wuhan University,Special Expert of national talent invitation program.His current research interests include the integration technology of largescale renewable energy,analysis of characteristics of DC-based renewable energy sources,control and operation of DC grids,DC transmission technologies,and key technologies of DC equipments.He has published over 200 journal papers,5 book chapters,and held 10 patents.He is the Chairman of IEC TC122 and the Convener of IEC TC8 JWG10.He is an IET Fellow,and an Associate Editor of CSEE Journal of Power Energy & System and IET Journal of High Voltage.He is also a Member of Editorial Board of Journal of IET Renewable Power Generation,Journal of Modern Power Systems and Clear Energy,Frontier in Energy,Proceedings of the CSEE and Power System Technology.

      • Fan Cheng

        Fan Cheng received the B.S.degree in electric engineering and automation from South China University of Technology,Guangzhou,Guangdong province,China in 2010 and the M.Eng.degree in electric engineering from Southeast University,Nanjing,Jiangsu province,China,in 2014.He is currently pursuing the Ph.Eng.degree in electric engineering at China electric power research institute,Beijing,China.His research interest includes the high voltage direct current technology,large scale renewable energy integration and interaction stability analysis of electronic power system.

      • Yan Li

        Yan Li received his B.S.degree from Shandong University of Technology in 1999,and received his M.S.degree from Fuzhou University in 2002,and received his Ph.D.degree from China Electric Power Research Institute (CEPRI) in 2007.Since 2007 he has been employed at CEPRI,presently as Renewable Energy Integration modeling and Simulation Research Division director of Renewable Energy Department of CEPRI.His interested researches are the power system analysis,renewable energy modeling and grid integration simulation,renewable energy develop planning.

      • Shuai Liang

        Shuai Liang received the B.S.and M.S.degrees in electrical engineering from Northeast Electric Power University,China,in 2015 and 2019.He is currently working toward the Ph.D.degree in Wuhan University.His research interests include renewable energy conversion systems and transient stability analysis.

      Publish Info

      Received:2020-01-05

      Accepted:2020-03-20

      Pubulished:2020-06-25

      Reference: Lijun Xie,Liangzhong Yao,Fan Cheng,et al.(2020) Coordinate control strategy for stability operation of offshore wind farm integrated with Diode-rectifier HVDC.Global Energy Interconnection,3(3):205-216.

      (Editor Dawei Wang)
      Share to WeChat friends or circle of friends

      Use the WeChat “Scan” function to share this article with
      your WeChat friends or circle of friends